Upload time:2025-06-04 Publisher:安立静
The chiller, circulating water pumps, and all connecting pipes in the machine room are rigidly fixed to the building structure, including the floor, roof, and walls.
The equipment relies solely on conventional rubber pads for vibration isolation, which proves insufficient during normal operation. As a result, vibrations are transmitted through the building structure to upper-floor tenants, leading to frequent complaints about vibration and noise.

Based on the site layout, each point requiring vibration isolation measures was identified and numbered, resulting in a total of 51 nodes in the plan.
The plan primarily covers:
2 screw chillers
6 air-conditioning water circulating pumps
2 plate heat vertical water pumps
The remaining nodes consist of pipeline support points, all of which are included in the vibration isolation scheme.

Screw Chillers
Each of the two screw chillers is fitted with a spring shock absorber on both the inner and outer sides of all four support vertical plates, ensuring that the vertical plates are fully separated from the foundation by 30–50 mm.
Pumps
A vibration damping pedestal with a spring damper is installed beneath each pump.
The pedestal weight is designed to be 1.0–1.5 times the weight of the pump.
The bolt holes of the shock absorber feet are positioned at least 10 cm away from the edge of the waterproof foundation.
Vertical Water Pumps in Plate Heat Exchanger Units
Each vertical water pump is installed on a vibration damping pedestal to ensure effective isolation and reduce vibration transmission.
A case of vibration and noise treatment of the energy computer room on the basement floor of a construction project in Hebei
2026-01-28
Strictly control the quality, and the quality is guaranteed!
2026-01-28
Hazards of roof equipment vibration
2026-01-28
A case of vibration reduction of an air-cooled module unit on the roof of a large hotel
2026-01-28
Vibration isolation characteristics of different types of pumps
2026-01-28
What are the reasons why air dampers do not inflate?
2026-01-28
Vibration remediation case of air conditioning equipment on the top floor
2026-01-28
Installation method of membrane air flotation damper
2026-01-28
Three-coordinate, roundness meter, microscope and other precision instruments shock absorption
2026-01-28
Why do cooling towers have vibration problems?
2026-01-28
Vibration isolation design of MAU computer room pipe support
2026-01-28
Vehicle, ship, aviation equipment control system, medical equipment, mobile electronic instruments buffer energy absorption
Material: 304 stainless steel plywo...
查看详情
Shock and vibration control of automotive, marine, aerospace, electronic, mechanical and other equipment
Material: stainless steel wire rope...
查看详情
Vibration isolation and buffering of vehicle-mounted, ship-based, cabinet chassis, camera, drone and other equipment
Material: 304 stainless steel wire ...
查看详情
Vibration isolation and buffering of on-board photography, aerial photography, communication devices, electronic sensing equipment, mobile electronic instruments, surveillance cameras, rocker arms and other equipment
Material: The upper and lower plate...
查看详情
Electronic devices that need to be resistant to strong impacts
Material: Thickened steel plate, ch...
查看详情
I don't know how to solve the low-frequency vibration problem of the equipment. Please contact the vibration reduction engineer at sale@anlijing.com